Ontario Septic Designer
This is what you hand the township.
A complete sample project — a 3-bedroom bungalow in Simcoe County — run through the same Part 8 engine the software uses. 20+ pages, three parts. Every number below is the engine’s real output.
Download the 20+ page sample (PDF) Run the free 2-minute check
The provincial application (the February 2026 version of the Application for a Permit to Construct or Demolish), Schedule 1 (designer), Schedule 2 (installer) and Schedule 3 (design specifications) — filled in, field by field, the way the counter clerk sees them every day.
Scaled site plan with setback distances, cross-section with grades and water table, setback report, soil logs and T-time summary — plus private cost sheets you keep at home.
Every number explained in plain English — why 3 bedrooms means 1,600 L/day, why the tank is 3,600 L, why the bed needs exactly 144 m of pipe, and what the inspector checks.
Daily design flow — the number that drives everything
| Number of bedrooms | Q |
|---|---|
| 1 bedroom | 750 L/day |
| 2 bedrooms | 1,100 L/day |
| 3 bedrooms ◄ this project | 1,600 L/day |
| 4 bedrooms | 2,000 L/day |
| 5 bedrooms | 2,500 L/day |
| Additional flow (largest of: bedrooms over 5, floor area over 200 m², fixture units over 20) | + 0 L |
| Total daily design flow Q | 1,600 L/day |
| Step | Value |
|---|---|
| 2 × Q = 2 × 1,600 | 3,200 L |
| Code minimum | 3,600 L |
| Minimum working capacity (greater governs) | 3,600 L |
| Selected: 3,600 L two-compartment tank with effluent filter | PASS |
Every distance, checked and shown
| Check | Required | Actual | Result |
|---|---|---|---|
| Septic tank to house | 1.5 m | 6.5 m | PASS |
| Septic tank to drilled well | 15 m | 18.4 m | PASS |
| Leaching bed to house | 5 m | 9.8 m | PASS |
| Leaching bed to drilled well (on site) | 15 m | 17.6 m | PASS |
| Leaching bed to neighbouring dug well | 30 m | 34 m | PASS |
| Leaching bed to property line | 3 m | 4.6 m | PASS |
| Reserve bed area shown and compliant | — | — | PASS |
The site plan and cross-section reviewers ask for
Priced from excavation dimensions, not textbook dimensions
| Item | Order | Subtotal |
|---|---|---|
| Septic tank 3,600 L, delivery, setting/crane | 1 | $4,000.00 |
| Distribution pipe, 10 ft lengths (473 ft + 20% waste) | 57 lengths | $1,425.00 |
| Clear septic stone (21.6 m³ + 10% waste) | 23.8 m³ | $1,953.12 |
| Filter fabric, fittings, marker stakes | lots | $510.00 |
| Excavator + operator (8 hr) and 2 labourers | 1 day | $2,560.00 |
| Permit / testing allowance | 1 | $1,100.00 |
| Subtotal before HST | $11,548.12 | |
| Total with HST | $13,049.38 | |
| Contractor quote entered: $32,000 → possible owner-builder savings | $18,950.62 |
Same engine. Your numbers. $99.99 + HST.
Designers charge $800–2,000 for this paperwork. Answer the questions, check every distance, print the package.
Build my package — $99.99 + HST Start with the free check
This sample is not a permit approval. Final approval is by the local building department, health unit, or approval authority.